What Size Wire Do I Need? AWG by Amps and Temperature Rating
For common home circuits the smallest copper wire is 14 AWG for 15 A, 12 AWG for 20 A and 10 AWG for 30 A. These follow NEC Table 310.16 and the small-conductor limits in 240.4(D). Aluminum needs a larger size. Long runs, bundled cables, heat and terminal ratings can require a larger wire, so treat any table result as a minimum.
Belongs to the guide: Complete Home Electrical Panel Labeling Guide for DIY Homeowners
Electrical Safety & YMYL Disclaimer: This guide provides general electrical information and is not a substitute for a licensed electrician or your local authority having jurisdiction (AHJ). Electrical work can cause fire, severe shock, and death. Always turn off the circuit breaker and verify the circuit is dead with a voltage tester before touching wiring. ESFI strongly recommends hiring a qualified, licensed electrician for electrical work, and the CPSC advises the same. Verify which NEC edition and local amendments apply in your area.
Wire size is set by the current the circuit carries and the breaker that protects it. This guide is part of our home panel and wiring guide. The minimum AWG calculator applies the same table and limits to your own numbers. Everything below is a minimum, and a licensed electrician decides the final size for your house.
What size wire for 15, 20, 30 and 40 amps?
For copper, 14 AWG is the smallest wire for a 15 A circuit, 12 AWG for 20 A and 10 AWG for 30 A. Those three sizes, and not the larger numbers in the ampacity table, are what NEC 240.4(D) allows you to protect with each breaker:
| Wire (copper) | Table 310.16 ampacity (60 / 75 / 90 °C) | Largest breaker (240.4(D)) |
|---|---|---|
| 14 AWG | 15 / 20 / 25 A | 15 A |
| 12 AWG | 20 / 25 / 30 A | 20 A |
| 10 AWG | 30 / 35 / 40 A | 30 A |
| 8 AWG | 40 / 50 / 55 A | no small-conductor cap; size by ampacity |
For a 40 A circuit, 8 AWG copper has 40 A in the 60 °C column and works as a minimum. For 50 A, 8 AWG is listed at 50 A only in the 75 °C column; in the 60 °C column that terminations often require (see below), the minimum is 6 AWG at 55 A. Ask a licensed electrician for any circuit above 30 A.
NEC Table 310.16 ampacity by AWG
Table 310.16 gives the allowable ampacity of insulated conductors by size, material and insulation temperature rating, with these conditions: not more than three current-carrying conductors in a raceway, cable or earth, and an ambient of 30 °C (86 °F). Selected values:
| Size | Copper 60 °C | Copper 75 °C | Copper 90 °C | Aluminum 60 °C | Aluminum 75 °C | Aluminum 90 °C |
|---|---|---|---|---|---|---|
| 14 AWG | 15 | 20 | 25 | no value | no value | no value |
| 12 AWG | 20 | 25 | 30 | 15 | 20 | 25 |
| 10 AWG | 30 | 35 | 40 | 25 | 30 | 35 |
| 8 AWG | 40 | 50 | 55 | 35 | 40 | 45 |
| 6 AWG | 55 | 65 | 75 | 40 | 50 | 55 |
| 4 AWG | 70 | 85 | 95 | 55 | 65 | 75 |
| 3 AWG | 85 | 100 | 115 | 65 | 75 | 85 |
| 2 AWG | 95 | 115 | 130 | 75 | 90 | 100 |
| 1 AWG | 110 | 130 | 145 | 85 | 100 | 115 |
Amperes. The table has no aluminum value for 14 AWG.
Copper vs aluminum
At the same size, aluminum carries less current: 12 AWG aluminum is 15 / 20 / 25 A against copper’s 20 / 25 / 30 A. Aluminum is also limited by 240.4(D) to 15 A of overcurrent protection on 12 AWG and 25 A on 10 AWG. Older homes may have aluminum branch wiring with a poor fire record; the CPSC and our signs your wiring needs an upgrade guide explain the warning signs. Do not splice or terminate aluminum without the right devices and a licensed electrician.
Breaker size vs wire size
The breaker protects the wire, so the wire must be rated for at least what the breaker allows, and small conductors have hard caps. Three rules matter at home:
- Small conductors (240.4(D)). 14 AWG copper to 15 A, 12 AWG copper to 20 A, 10 AWG copper to 30 A; aluminum 12 AWG to 15 A and 10 AWG to 25 A.
- Continuous loads (210.20(A)). For loads that run three hours or more, the breaker must be at least the noncontinuous load plus 125% of the continuous load, and the conductor ampacity must be at least that as well (210.19(A)(1)).
- Temperature limits (110.14(C)). For equipment on circuits of 100 A or less, terminations are generally based on the 60 °C column, unless the equipment is listed and marked for higher. Wire with a higher rating may be used for ampacity adjustment and correction, but the termination limit still applies.
The outlets per 20 amp circuit guide shows how the 125% rule limits a 20 A circuit to 16 A of continuous load.
Derating, long runs and heat
Table 310.16 is a starting point. Table 310.15(C)(1) multiplies the ampacity by 80% for 4 to 6 current-carrying conductors in the same cable or raceway, 70% for 7 to 9 and 50% for 10 to 20. Hot attics and sun-exposed runs apply ambient temperature correction from Table 310.15(B)(1). Long runs add voltage drop; our voltage drop formula guide shows that 12 AWG copper at 20 A is within 3% for about 45 ft one way and 8 AWG for about 115 ft.
Worked example: a 32 A continuous load
A fixed 32 A load that runs for hours is a continuous load. The minimum conductor ampacity is 32 × 1.25 = 40 A.
- Copper, 60 °C column: 10 AWG lists 30 A, not enough. 8 AWG lists 40 A. The minimum is 8 AWG.
- Aluminum, 60 °C column: 8 AWG lists 35 A, not enough. 6 AWG lists 40 A. The minimum is 6 AWG.
- A 40 A breaker is the matching overcurrent device (the load plus 125%).
If the run is 120 ft one way at 240 V, check voltage drop too: 8 AWG copper drops 2 × 12.9 × 32 × 120 ÷ 16,510 = 6.00 V, which is 2.50% of 240 V, within the 3% guidance. Derating factors, terminals and local code can still require a larger wire, which is why the final call belongs to a licensed electrician.
When to hire a licensed electrician
Call one when you are adding a circuit, changing a breaker, working in the panel, dealing with aluminum or knob-and-tube wiring, or if the wire gets warm. ESFI “strongly recommends hiring a qualified, licensed electrician,” and a permit and inspection may be required where you live. Use the wire size calculator to plan and compare, not to replace that professional.
Answers to common questions
What gauge wire do I need for a 20 amp circuit?
12 AWG copper is the smallest wire allowed on a 20 A breaker. NEC 240.4(D) limits 14 AWG copper to 15 A of overcurrent protection, and 12 AWG copper to 20 A. Aluminum 12 AWG is limited to 15 A, so a 20 A aluminum circuit needs 10 AWG. Long runs may need a larger wire to limit voltage drop, so check the length too.
Can I use 12 AWG wire on a 30 amp breaker?
No. NEC 240.4(D) caps overcurrent protection at 20 A for 12 AWG copper, even though Table 310.16 lists 12 AWG at 25 to 30 A in the 75 and 90 °C columns. A 30 A circuit needs 10 AWG copper at minimum. Putting 12 AWG on a 30 A breaker leaves the wire unprotected from overload, which can overheat the insulation.
Does aluminum wire need a bigger gauge than copper?
Yes. Aluminum carries less current at the same size. In Table 310.16's 75 °C column, 8 AWG copper is 50 A while 8 AWG aluminum is 40 A, so you usually go up one size. Aluminum also needs terminals rated for it and has its own small-conductor limits. Leave aluminum work to a licensed electrician.
What is the difference between the 60 °C and 75 °C columns?
The columns give a wire's ampacity based on the temperature rating used. Under NEC 110.14(C), terminations on circuits of 100 A or less are generally sized on the 60 °C column unless the equipment is listed and marked for higher. So even with 75 °C wire, many home devices mean the 60 °C ampacity applies. Use the lowest rating among wire, breaker and device.
How does wire length change the gauge I need?
Length does not change the ampacity, but it raises voltage drop, which may call for a larger gauge. The NEC's informational notes suggest keeping drop to about 3% on a branch circuit. For a 20 A, 120 V copper circuit, 12 AWG stays within 3% for about 45 ft one way, 10 AWG for about 72 ft and 8 AWG for about 115 ft.
Evidence and sources
- NFPA 70 (NEC) 2020 text as reproduced in the 2022 California Electrical Code: Table 310.16, 240.4(D), 110.14(C), 210.20(A), Table 310.15(C)(1) (law.resource.org)
- IAEI Magazine: Voltage Drop Formulas (from Ferm's Formulas and Calculations, 2014) (iaeimagazine.org)
- ESFI: Do-It-Yourself (DIY) Electrical Safety (esfi.org)
- CPSC: Plug into Safety! (NSN 18-07) (cpsc.gov)
- Complete Home Electrical Panel Labeling Guide for DIY Homeowners
Learn how to map and label your home electrical panel safely without removing the dead-front cover, following NEC 408.4(A) circuit directory standards.
- Voltage Drop Calculator and Formula: Copper vs Aluminum Wire
Voltage drop formula for copper and aluminum wire with the NEC 3% and 5% guidance, a worked 100 ft example, and when to step up to a larger gauge.
- Signs Your Home Wiring Needs an Upgrade: A DIY Homeowner's Guide
Spot the 10 warning signs your home wiring needs an upgrade—from frequent breaker trips to aluminum and knob-and-tube wiring—and know when to call a pro.