Voltage Drop Calculator and Formula: Copper vs Aluminum Wire

By Reviewed by Home Circuitry HQ Editorial Team Last reviewed Published on Category: Residential Wiring

Voltage drop on a single-phase circuit is VD = 2 × K × I × L ÷ CM, where K is 12.9 for copper or 21.2 for aluminum, I is amps, L is the one-way length in feet and CM is the wire's circular mils. The NEC's informational notes suggest keeping drop to 3% on a branch circuit and 5% overall. They are recommendations, not requirements.

Coils of insulated cable beside a tape measure on a bench

Belongs to the guide: Complete Home Electrical Panel Labeling Guide for DIY Homeowners

Electrical Safety & YMYL Disclaimer: This guide provides general electrical information and is not a substitute for a licensed electrician or your local authority having jurisdiction (AHJ). Electrical work can cause fire, severe shock, and death. Always turn off the circuit breaker and verify the circuit is dead with a voltage tester before touching wiring. ESFI strongly recommends hiring a qualified, licensed electrician for electrical work, and the CPSC advises the same. Verify which NEC edition and local amendments apply in your area.

Voltage drop is the voltage a wire loses between the panel and the load. It grows with current and length and shrinks with a bigger conductor. This guide is part of our home panel and wiring guide, and you can run your own numbers in our free tool for volts lost on a circuit as you read.

How much voltage drop is acceptable?

Aim for about 3% or less on a branch circuit and about 5% or less from the service to the farthest outlet. Those figures come from informational notes in the National Electrical Code, under 210.19(A) for branch circuits and 215.2(A)(1) for feeders. The notes say that conductors sized to those limits provide reasonable efficiency of operation. An informational note explains the code but is not itself a requirement, so a drop of 4% is not a code violation by that note alone, and your local authority can still ask for something different.

On a 120 V circuit, 3% is 3.6 V, so the load sees about 116.4 V. On 240 V, 3% is 7.2 V. Percentages scale with system voltage, which is why a long 240 V run tolerates more volts of drop than a 120 V run of the same length.

The voltage drop formula

For a single-phase circuit, the circular-mil method is:

VD = 2 × K × I × L ÷ CM

  • VD: volts lost along the circuit.
  • K: a constant for the conductor material, in ohm-circular mils per foot at 75 °C.
  • I: load current in amperes.
  • L: one-way length in feet, from the panel to the load along the cable route. The factor 2 covers the round trip.
  • CM: the conductor’s area in circular mils, from NEC Chapter 9, Table 8.

Percent drop is VD ÷ system voltage × 100. For three-phase circuits the 2 becomes 1.732, the square root of 3. Rearranged, the longest run for a target is L = CM × (target % ÷ 100 × voltage) ÷ (2 × K × I), and the circular mils needed for a given run are CM = 2 × K × I × L ÷ (target % ÷ 100 × voltage).

This is a direct-current resistance method at 75 °C. It ignores reactance and power factor, which matter on large conductors and long AC runs, and a hot conductor drops slightly more. For home branch circuits it is a standard planning figure.

Copper vs aluminum constants

The constants come from the DC resistance values in Chapter 9, Table 8, multiplied by the circular mil area, as published by the IAEI:

Copper uses K = 12.9 and aluminum K = 21.2 (compared in the table below).

Because 21.2 ÷ 12.9 = 1.64, an aluminum conductor needs about 64% more area than copper for the same voltage drop. In practice that is roughly two AWG sizes larger. Aluminum branch wiring also has its own overcurrent limits under 240.4(D) (12 AWG aluminum is limited to 15 A, 10 AWG to 25 A) and special termination requirements, so a size that passes the drop test may still be wrong for the breaker. Our wire size guide covers those limits.

Worked example: a 100 ft, 20 A run

A 20 A load on a 120 V circuit, 100 ft one way. For copper:

  • 12 AWG (6,530 CM): 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.90 V, 6.58%.
  • 10 AWG (10,380 CM): 4.97 V, 4.14%.
  • 8 AWG (16,510 CM): 3.13 V, 2.60%.
  • 6 AWG (26,240 CM): 1.97 V, 1.64%.

To land at 3%, the circular mils needed are 2 × 12.9 × 20 × 100 ÷ (0.03 × 120) = 14,333, so the first standard size above that is 8 AWG. For aluminum on the same run:

  • 10 AWG (K = 21.2): 8.17 V, 6.81%.
  • 8 AWG: 5.14 V, 4.28%.
  • 6 AWG: 3.23 V, 2.69%.

The 12 AWG aluminum row is left out because that size is limited to 15 A of overcurrent protection. Aluminum takes 6 AWG to get inside 3% where copper takes 8 AWG.

How far can each wire go?

At 20 A on 120 V and a 3% target, the longest one-way run from L = CM × 3.6 ÷ (2 × K × 20) is:

Wire Copper Aluminum
12 AWG 45.6 ft 27.7 ft (not for 20 A, see note above)
10 AWG 72.4 ft 44.1 ft
8 AWG 115.2 ft 70.1 ft

Lower the current and the allowed length rises in proportion: the same copper 12 AWG wire carrying 15 A can run 60.7 ft within 3%.

When to choose a larger gauge

Consider stepping up when:

  1. The run is long, such as a detached garage, a shed, outdoor lighting or a well pump.
  2. The load is sensitive to low voltage, such as motors and pumps, where low voltage raises current and heat.
  3. You are already near the 3% target and plan to add load later.

Going from 12 to 10 AWG, or from 10 to 8 AWG, multiplies the circular mils by about 1.6 and so cuts the drop by about 37%, which often fixes a borderline run. A larger conductor is harder to terminate and may need bigger conduit or a device rated for it, so confirm that before you buy. A licensed electrician sizes the final circuit, including the breaker and the equipment grounding conductor.

Worked example: a long outdoor run

A 30 A, 240 V single-phase feed to a detached workshop 150 ft away, in copper:

  • 10 AWG: 2 × 12.9 × 30 × 150 ÷ 10,380 = 11.18 V, 4.66% of 240 V.
  • 8 AWG: 7.03 V, 2.93%, within 3%.
  • 6 AWG: 4.42 V, 1.84%.

In aluminum, 8 AWG gives 4.82% and 6 AWG gives 3.03%, so 4 AWG (1.90%) is the first size inside 3%. Underground and outbuilding feeds also bring rules for burial depth, disconnects and grounding that this page does not cover. That is a job for a licensed electrician and a permit.

Limits of this formula

  • The 3% and 5% figures are recommendations. Equipment makers may require less, and specific NEC sections set limits for specific systems.
  • The result is voltage drop only. It does not check ampacity, the small-conductor limits or the breaker size. See how many outlets fit on a 20 amp circuit for how circuit loading works.
  • Charging an electric vehicle is a continuous load on a long circuit, where drop and heat both matter. See our EV charging guide and the NEMA 14-50 outlet guide, and have a licensed electrician size it.
  • Flickering lights, warm outlets or breakers that trip are signs to stop and have the circuit checked. Our guide to signs your wiring needs an upgrade lists them.

To try your own circuit, open the voltage drop calculator. For sizing the wire itself, use the minimum AWG tool next.

Copper vs aluminum voltage drop at a glance (120 V, 20 A, 100 ft one way)
FeatureCopperAluminum
K (ohm-cmil per ft, 75 °C)12.921.2
Circular mils needed for the same drop1.00×1.64×
10 AWG voltage drop4.97 V (4.14%)8.17 V (6.81%)
8 AWG voltage drop3.13 V (2.60%)5.14 V (4.28%)
First size within 3%8 AWG6 AWG

Copper stays within 3% two sizes smaller than aluminum on this run. Choose by the drop first, then confirm ampacity, breaker limits and terminals with a licensed electrician.

Answers to common questions

What voltage drop is acceptable in a home circuit?

The NEC does not set a mandatory limit for ordinary branch circuits. Its informational notes say that sizing conductors for no more than 3% drop at the farthest outlet, and no more than 5% total on feeder and branch circuit together, provides reasonable efficiency of operation. These are recommendations, so local amendments or the equipment maker's instructions can ask for less. A licensed electrician applies the rules your local authority has adopted.

How do I calculate voltage drop on a 100 ft, 20 A run?

Use VD = 2 × K × I × L ÷ CM. For copper, 12 AWG (6,530 circular mils): 2 × 12.9 × 20 × 100 ÷ 6,530 = 7.90 V, which is 6.58% of 120 V. 10 AWG gives 4.14% and 8 AWG gives 2.60%. So on this run 8 AWG is the first copper size within 3%. The calculation covers voltage drop only; the wire must also suit the breaker.

Does aluminum wire drop more voltage than copper?

Yes. Aluminum's k-factor is 21.2 against 12.9 for copper, so at the same size aluminum drops about 64% more voltage. To match copper you step up roughly two AWG sizes. For example, 10 AWG aluminum drops 6.81% on the 100 ft, 20 A example where 10 AWG copper drops 4.14%. Aluminum also has its own termination and overcurrent limits, so ask a licensed electrician.

When should I use a larger wire to reduce voltage drop?

Consider a larger gauge when a long run pushes the calculated drop above 3% on a branch circuit, or when a load is sensitive to low voltage, such as motors, pumps and tools. Moving up two AWG sizes (for example 12 to 10) cuts the drop by about 37%, because the circular mils grow about 1.6 times. A larger wire is also a bigger conductor to terminate, so check the device terminals and conduit size.

Is the 3% voltage drop figure a code requirement?

No. In the 2020 NEC, the 3% and 5% numbers appear in informational notes under 210.19(A) and 215.2(A)(1), and the NEC defines informational notes as explanatory material, not enforceable requirements. Some other sections do set drop limits for specific systems, and local codes can add rules. Treat 3% and 5% as good-practice targets, and confirm local requirements with your authority having jurisdiction.

Evidence and sources

  1. IAEI Magazine: Voltage Drop Formulas (from Ferm's Formulas and Calculations, 2014) (iaeimagazine.org)
  2. NFPA 70 (NEC) 2020 text as reproduced in the 2022 California Electrical Code: 210.19(A) and 215.2(A)(1) informational notes, Chapter 9 Table 8 (law.resource.org)